Whilst all efforts are made to provide accurate and timely information from the relevant source/documentation, please be aware that the information supplied may not be the most current version. The accuracy of the detail has not been confirmed by the Department and therefore should not be relied upon without first confirming the contents.

Verify compliance and functionality of low voltage general electrical installations

Verify compliance and functionality of low voltage general electrical installations

Unit of competency
National Code
UEENEEG105A
State Code
S7322
TGA Status
Replaced
DTWD Status
Replaced
Current Release Number
4.00
Current Release Date
14/08/2013
State Implementation and Classification
Approved Date
29/10/2014
Field of Education
031313 - Electrical Fitting, Electrical Mechanics
Original Release Date
29/10/2014
Nominal Hours
36
Description
1) 1.1) DescriptorThis unit covers inspection and testing to verify whether an electrical installation is safe and complies with all requirements. It encompasses working safely, visual inspections and mandatory, optional and functional testing following verification procedures, identifying non-compliance defects and mandatory reporting requirements.
Notes
Elements and Performance Criteria
1 Prepare to inspect and test an electrical installation.
  • 1.1 OHS measures for the site are identified, obtained and understood.
  • 1.2 Established OHS risk control measures and procedures in preparation for the work are followed.
  • 1.3 Safety hazards, which have not previously been identified, are noted and established risk control measures are implemented.
  • 1.4 Documentation or deemed to comply standard on which installation is based is reviewed and understood.
  • 1.5 Appropriate personnel are consulted to ensure the work is coordinated effectively with others involved on the work site.
  • 1.6 Tools, equipment and testing devices needed to verify compliance are obtained in accordance with established procedures and checked for correct operation and safety.
  • 1.7 Preparatory work is checked to ensure no damage has occurred and complies with requirements.
2 Visually inspect and conduct safety testing on the installation.
  • 2.1 OHS risk control measures and procedures for carrying out the work are followed.
  • 2.2 The need to test or measure live is determined in strict accordance with OHS requirements and when necessary conducted within established safety procedures.
  • 2.3 Circuits/machines/plant are checked as being isolated where necessary in strict accordance OHS requirements and procedures.
  • 2.4 Wiring is checked for suitability for the environments in which they are installed and suitably protected from damage or overheating.
  • 2.5 Cable conductor sizes are confirmed as meeting current-carrying capacity requirements and voltage-drop and fault-loop impedance limitations.
  • 2.6 Protection methods and devices are validated as meeting co-ordination requirements for overload and short-circuit protection.
  • 2.7 Switchgear and control gear is validated as being appropriately rated and meeting functional requirements.
  • 2.8 Evidence that electrical equipment complies with safety requirements is cited.
  • 2.9 Earthing system components are checked that they are correctly located and conductors correctly sized.
  • 2.10 Marking on switchboards are checked for accuracy and clarity and comply with requirements.
  • 2.11 Mandatory tests are conducted to verify that: earthing conductor resistance is sufficiently low; insulation resistance is sufficiently high; all polarities are correct; and circuit connections are correct as per AS/NZS3000.
  • 2.12 Testing is conducted to verify that: fault-loop impedance is sufficiently low and residual current devices operates as intended as per AS/NZS3000.
3 Report inspection and test findings.
  • 3.1 OHS risk control work completion measures and procedures are followed.
  • 3.2 Work site is cleaned and made safe in accordance with established procedures.
  • 3.3 Non-compliance defects are identified and reported in accordance with established procedures.
  • 3.4 Recommendations for rectifying defects are made in accordance with established procedures.
  • 3.5 Mandatory documentation is completed in accordance with established procedures.
RANGE STATEMENT
8) This relates to the unit as a whole providing the range of contexts and conditions to which the performance criteria apply. It allows for different work environments and situations that will affect performance.
This unit shall be demonstrated in relation to verifying compliance and functionality of at least two general electrical installations comprising a main switchboard, supplying more than one circuit each for, lighting, socket outlets, and fixed appliances. One of the installations shall include a distribution board separate from the main switchboard and at least one circuit supplying a three-phase load and a safety system.
Generic terms used throughout this Vocational Standard shall be regarded as part of the Range Statement in which competency is demonstrated. The definition of these and other terms that apply are given in Volume 2, Part 2.1.
EVIDENCE GUIDE
9) The evidence guide provides advice on assessment and must be read in conjunction with the Performance Criteria, Required Skills and Knowledge, the Range Statement and the Assessment Guidelines for this Training Package.
The Evidence Guide forms an integral part of this unit. It must be used in conjunction with all parts of this unit and performed in accordance with the Assessment Guidelines of this Training Package.
Overview of Assessment
9.1)
Longitudinal competency development approaches to assessment, such as Profiling, require data to be reliably gathered in a form that can be consistently interpreted over time. This approach is best utilised in Apprenticeship programs and reduces assessment intervention. It is the Industry's preferred model for apprenticeships. However, where summative (or final) assessment is used it is to include the application of the competency in the normal work environment or, at a minimum, the application of the competency in a realistically simulated work environment. It is recognised that, in some circumstances, assessment in part or full can occur outside the workplace. However, it must be in accordance with industry and regulatory policy.
Methods chosen for a particular assessment will be influenced by various factors. These include the extent of the assessment, the most effective locations for the assessment activities to take place, access to physical resources, additional safety measures that may be required and the critical nature of the competencies being assessed.
The critical safety nature of working with electricity, electrical equipment, gas or any other hazardous substance/material carries risk in deeming a person competent. Sources of evidence need to be 'rich' in nature to minimise error in judgment.
Activities associated with normal every day work have a bearing on the decision as to how much and how detailed the data gathered will contribute to its 'richness'. Some skills are more critical to safety and operational requirements while the same skills may be more or less frequently practised. These points are raised for the assessors to consider when choosing an assessment method and developing assessment instruments. Sample assessment instruments are included for Assessors in the Assessment Guidelines of this Training Package.
Critical aspects of evidence required to demonstrate competency in this unit
9.2)
Before the critical aspects of evidence are considered all prerequisites shall be met.
Evidence for competence in this unit shall be considered holistically. Each element and associated performance criteria shall be demonstrated on at least two occasions in accordance with the 'Assessment Guidelines - UEE07'. Evidence shall also comprise:
A representative body of work performance demonstrated within the timeframes typically expected of the discipline, work function and industrial environment. In particular this shall incorporate evidence that shows a candidate is able to:

Implement Occupational Health and Safety workplace procedures and practices including the use of risk control measures as specified in the performance criteria and range statement
Apply sustainable energy principles and practices as specified in the performance criteria and range statement
Demonstrate an understanding of the essential knowledge and associated skills as described in this unit. It may be required by some jurisdictions that RTOs provide a percentile graded result for the purpose of regulatory or licensing requirements.
Demonstrate an appropriate level of skills enabling employment
Conduct work observing the relevant Anti Discrimination legislation, regulations, polices and workplace procedures

Demonstrated consistent performance across a representative range of contexts from the prescribed items below:

Verify compliance and functionality of general electrical installations as described as described in 8) and including:


A
Selecting correct tools and testing equipment.


B
Identifying visual non-compliance defects.


C
Using effective methods for conducting mandatory and optional tests.


D
Identifying non-compliance from test results.


E
Identifying causes of non-compliance.


F
Completing mandatory reporting.


G
Dealing with unplanned events
Context of and specific resources for assessment
9.3)
This unit should be assessed as it relates to normal work practice using procedures, information and resources typical of a workplace. This should include:
OHS policy and work procedures and instructions.
Suitable work environment, facilities, equipment and materials to undertake actual work as prescribed by this unit.
These should be part of the formal learning/assessment environment.
Note:
Where simulation is considered a suitable strategy for assessment, conditions must be authentic and as far as possible reproduce and replicate the workplace and be consistent with the approved industry simulation policy.

The resources used for assessment should reflect current industry practices in relation to verifying compliance and functionality of general electrical installations.
Method of assessment
9.4)
This unit shall be assessed by methods given in Volume 1, Part 3 'Assessment Guidelines'.
Note: Competent performance with inherent safe working practices is expected in the industry to which this unit applies. This requires assessment in a structured environment which is primarily intended for learning/assessment and incorporates all necessary equipment and facilities for learners to develop and demonstrate the essential knowledge and skills described in this unit.
Concurrent assessment and relationship with other units
9.5)
There are no concurrent assessment recommendations for this unit.
Replaces
State Code National Code Title Type
W7884 UEENEEG005B Verify compliance and functionality of general electrical installations Unit of competency
Replaced By
State Code National Code Title Type
OBY86 UEEEL0039 Design, install and verify compliance and functionality of general electrical installations Unit of competency
State Code National Code Title Type
A136 UEE40511 Certificate IV in Electrical - Air-conditioning Split Systems Qualification
A133 UEE40211 Certificate IV in Electrical - Data and Voice Communications Qualification
D642 UEE62211 Advanced Diploma of Electrical - Engineering Qualification
A139 UEE40811 Certificate IV in Electrical - Fire Protection Control Systems Qualification
A135 UEE40411 Certificate IV in Electrical - Instrumentation Qualification
A142 UEE41111 Certificate IV in Electrical - Lift Systems Qualification
A149 UEE42011 Certificate IV in Electrical - Photovoltaic systems Qualification
A143 UEE41211 Certificate IV in Electrical - Rail Signalling Qualification
A147 UEE41911 Certificate IV in Electrical - Renewable Energy Qualification
A156 UEE50211 Diploma of Electrical and Instrumentation Qualification
A157 UEE50311 Diploma of Electrical and Refrigeration and Air-conditioning Qualification
A158 UEE50411 Diploma of Electrical Engineering Qualification
A148 UEE42111 Certificate IV in Electrotechnology - Electrical Contracting Qualification
A138 UEE40611 Certificate IV in Electrotechnology - Systems Electrician Qualification
A123 UEE30811 Certificate III in Electrotechnology Electrician Qualification
A153 UEE43111 Certificate IV in Energy Efficiency and Assessment Qualification
A141 UEE41011 Certificate IV in Energy Management and Control Qualification
A170 UEE61211 Advanced Diploma of Engineering - Explosion protection Qualification
J169 UET40612 Certificate IV in ESI - Power Systems Network Infrastructure Qualification
BHB1 UET40621 Certificate IV in ESI - Power Systems Network Infrastructure Qualification
BEV3 UET40619 Certificate IV in ESI - Power Systems Network Infrastructure Qualification
BHB2 UET40521 Certificate IV in ESI - Power Systems Substations Qualification
J168 UET40512 Certificate IV in ESI - Power Systems Substations Qualification
BEV5 UET40519 Certificate IV in ESI - Power Systems Substations Qualification
A151 UEE42611 Certificate IV in Hazardous areas - Electrical Qualification
A140 UEE40911 Certificate IV in Industrial Electronics and Control Qualification
A162 UEE50911 Diploma of Industrial Electronics and Control Engineering Qualification
A167 UEE60611 Advanced Diploma of Industrial Electronics and Control Engineering Qualification
A134 UEE40311 Certificate IV in Installation Inspection and Audits Qualification
A159 UEE50711 Diploma of Renewable Energy Engineering Qualification
A168 UEE60911 Advanced Diploma of Renewable Energy Engineering Qualification