Whilst all efforts are made to provide accurate and timely information from the relevant source/documentation, please be aware that the information supplied may not be the most current version. The accuracy of the detail has not been confirmed by the Department and therefore should not be relied upon without first confirming the contents.
Install and commission carbon dioxide refrigeration systems, components and associated equipment
Install and commission carbon dioxide refrigeration systems, components and associated equipment
Unit of competency
National Code
UEENEEJ186A
UEENEEJ186A
State Code
S7415
S7415
TGA Status
Replaced
Replaced
DTWD Status
Replaced
Replaced
State Implementation and Classification
Approved Date
13/01/2012
Field of Education
031315 - Refrigeration And Air Conditioning Mechanics
Original Release Date
13/01/2012
Nominal Hours
18
Description
1) 1.1) DescriptorThis unit covers specialised procedures for the installation and commissioning to achieve effective and efficient operation of refrigeration equipment using carbon dioxide (CO2) as a refrigerant excluding self contained systems. It reinforces safe working practice and encompasses applying specialised knowledge of refrigeration principles that apply to carbon dioxide, following design specifications, testing, locating and rectifying faults and defective components and completing the necessary installation and commissioning documentation.
Notes
Elements and Performance Criteria
No information
RANGE STATEMENT
8) This relates to the unit as a whole providing the range of contexts and conditions to which the performance criteria apply. It allows for different work environments and situations that will affect performance.
This unit must be demonstrated in relation to determining operating conditions using measurement and basic calculation methods of carbon dioxide vapour compression and volatile secondary (liquid recirculation) system.
Furthermore, this unit must be demonstrated in relation to installing, connecting and commissioning the following Carbon Dioxide refrigeration system and components and associated equipment.
Major components shall include compressors, cascade condensers, evaporators, liquid recirculation pump/s. Associated equipment shall include refrigerant piping, refrigerant flow controls, cycling controls, safety controls, relief valves, isolation valves, monitoring and inspection accessories. Note: Steel pipe welding competency is not covered by this unit.
Generic terms used throughout this Vocational Standard shall be regarded as part of the Range Statement in which competency is demonstrated. The definition of these and other terms that apply are given in Volume 2, Part 2.1.
8) This relates to the unit as a whole providing the range of contexts and conditions to which the performance criteria apply. It allows for different work environments and situations that will affect performance.
This unit must be demonstrated in relation to determining operating conditions using measurement and basic calculation methods of carbon dioxide vapour compression and volatile secondary (liquid recirculation) system.
Furthermore, this unit must be demonstrated in relation to installing, connecting and commissioning the following Carbon Dioxide refrigeration system and components and associated equipment.
Major components shall include compressors, cascade condensers, evaporators, liquid recirculation pump/s. Associated equipment shall include refrigerant piping, refrigerant flow controls, cycling controls, safety controls, relief valves, isolation valves, monitoring and inspection accessories. Note: Steel pipe welding competency is not covered by this unit.
Generic terms used throughout this Vocational Standard shall be regarded as part of the Range Statement in which competency is demonstrated. The definition of these and other terms that apply are given in Volume 2, Part 2.1.
EVIDENCE GUIDE
9) The evidence guide provides advice on assessment and must be read in conjunction with the Performance Criteria, Required Skills and Knowledge, the Range Statement and the Assessment Guidelines for this Training Package. .
The Evidence Guide forms an integral part of this Unit. It must be used in conjunction with all parts of this unit and performed in accordance with the Assessment Guidelines of this Training Package.
Overview of Assessment
9.1)
Longitudinal competency development approaches to assessment, such as Profiling, require data to be reliably gathered in a form that can be consistently interpreted over time. This approach is best utilised in Apprenticeship programs and reduces assessment intervention. It is the industry-preferred model for apprenticeships. However, where summative (or final) assessment is used it is to include the application of the competency in the normal work environment or, at a minimum, the application of the competency in a realistically simulated work environment. In some circumstances, assessment in part or full can occur outside the workplace. However, it must be in accordance with industry and regulatory policy.
Methods chosen for a particular assessment will be influenced by various factors. These include the extent of the assessment, the most effective locations for the assessment activities to take place, access to physical resources, additional safety measures that may be required and the critical nature of the competencies being assessed.
The critical safety nature of working with electricity, electrical equipment, gas or any other hazardous substance/material carries risk in deeming a person competent. Sources of evidence need to be 'rich' in nature to minimise error in judgment.
Activities associated with normal everyday work influence decisions about how/how much the data gathered will contribute to its 'richness'. Some skills are more critical to safety and operational requirements while the same skills may be more or less frequently practised. These points are raised for the assessors to consider when choosing an assessment method and developing assessment instruments. Sample assessment instruments are included for Assessors in the Assessment Guidelines of this Training Package.
Critical aspects of evidence required to demonstrate competency in this unit
9.2)
Before the critical aspects of evidence are considered all prerequisites shall be met.
Evidence for competence in this unit shall be considered holistically. Each element and associated performance criteria shall be demonstrated on at least two occasions in accordance with the 'Assessment Guidelines - UEE07'. Evidence shall also comprise:
A representative body of work performance demonstrated within the timeframes typically expected of the discipline, work function and industrial environment. In particular this shall incorporate evidence that shows a candidate is able to:
Implement Occupational Health and Safety workplace procedures and practices including the use of risk control measures as specified in the performance criteria and range statement
Apply sustainable energy principles and practices as specified in the performance criteria and range statement
Demonstrate an understanding of the essential knowledge and associated skills as described in this unit. It may be required by some jurisdictions that RTOs provide a percentile graded result for the purpose of regulatory or licensing requirements.
Demonstrate an appropriate level of skills enabling employment
Conduct work observing the relevant Anti Discrimination legislation, regulations, polices and workplace procedures
Demonstrated consistent performance across a representative range of contexts from the prescribed items below:
Install CO2 refrigeration system components pipe work and associated equipment including :
A
Reading and interpreting drawings to pipe work layouts and apparatus locations.
B
Installing, connecting , securing and aligning components and equipment and ensuring that all equipment and pipe work is compliant with codes and regulations
C
Pressure testing entire system at the appropriate design test pressures using dry nitrogen
D
Removing system contaminants and evacuating
E
Selecting and using appropriate measuring devices correctly
F
Recording measurements
G
Using calculation methods accurately
H
Discharging / charging refrigerant / lubricants and pressure testing the system without damage to components
I
Locating and rectifying leaks
J
Using methodical and efficient commissioning techniques
K
Optimizing system performance and efficiency
L
Identifying the conditions of the refrigerant (R744) at various locations in the vapour compression and volatile secondary (liquid recirculation) system
M
Documenting operating conditions correctly (commissioning)
N
Dealing with unplanned events by drawing on essential knowledge and skills to provide appropriate solutions incorporated in the holistic assessment with the above listed items
Context of and specific resources for assessment
9.3)
This unit should be assessed as it relates to normal work practice using procedures, information and resources typical of a workplace. This should include:
OHS policy and work procedures and instructions.
Suitable work environment, facilities, equipment and materials to undertake actual work as prescribed by this unit.
These should be part of the formal learning/assessment environment.
Note:
Where simulation is considered a suitable strategy for assessment, conditions must be authentic and as far as possible reproduce and replicate the workplace and be consistent with the approved industry simulation policy.
Evidence should show demonstrated competency in installation techniques as well as Commissioning skills and a clear understanding of operating conditions of Carbon Dioxide vapour compression and volatile secondary (liquid recirculation/cascade) system/s.
Method of assessment
9.4)
This unit shall be assessed by methods given in Volume 1, Part 3 'Assessment Guidelines'.
Note:
Competent performance with inherent safe working practices is expected in the industry to which this unit applies. This requires assessment in a structured environment which is primarily intended for learning/assessment and incorporates all necessary equipment and facilities for learners to develop and demonstrate the essential knowledge and skills described in this unit.
Concurrent assessment and relationship with other units
9.5)
There are no concurrent assessment recommendations for this unit.
The critical aspects of occupational health and safety covered in unit UEENEEE001B and other discipline specific occupational health and safety units shall be incorporated in relation to this unit..
9) The evidence guide provides advice on assessment and must be read in conjunction with the Performance Criteria, Required Skills and Knowledge, the Range Statement and the Assessment Guidelines for this Training Package. .
The Evidence Guide forms an integral part of this Unit. It must be used in conjunction with all parts of this unit and performed in accordance with the Assessment Guidelines of this Training Package.
Overview of Assessment
9.1)
Longitudinal competency development approaches to assessment, such as Profiling, require data to be reliably gathered in a form that can be consistently interpreted over time. This approach is best utilised in Apprenticeship programs and reduces assessment intervention. It is the industry-preferred model for apprenticeships. However, where summative (or final) assessment is used it is to include the application of the competency in the normal work environment or, at a minimum, the application of the competency in a realistically simulated work environment. In some circumstances, assessment in part or full can occur outside the workplace. However, it must be in accordance with industry and regulatory policy.
Methods chosen for a particular assessment will be influenced by various factors. These include the extent of the assessment, the most effective locations for the assessment activities to take place, access to physical resources, additional safety measures that may be required and the critical nature of the competencies being assessed.
The critical safety nature of working with electricity, electrical equipment, gas or any other hazardous substance/material carries risk in deeming a person competent. Sources of evidence need to be 'rich' in nature to minimise error in judgment.
Activities associated with normal everyday work influence decisions about how/how much the data gathered will contribute to its 'richness'. Some skills are more critical to safety and operational requirements while the same skills may be more or less frequently practised. These points are raised for the assessors to consider when choosing an assessment method and developing assessment instruments. Sample assessment instruments are included for Assessors in the Assessment Guidelines of this Training Package.
Critical aspects of evidence required to demonstrate competency in this unit
9.2)
Before the critical aspects of evidence are considered all prerequisites shall be met.
Evidence for competence in this unit shall be considered holistically. Each element and associated performance criteria shall be demonstrated on at least two occasions in accordance with the 'Assessment Guidelines - UEE07'. Evidence shall also comprise:
A representative body of work performance demonstrated within the timeframes typically expected of the discipline, work function and industrial environment. In particular this shall incorporate evidence that shows a candidate is able to:
Implement Occupational Health and Safety workplace procedures and practices including the use of risk control measures as specified in the performance criteria and range statement
Apply sustainable energy principles and practices as specified in the performance criteria and range statement
Demonstrate an understanding of the essential knowledge and associated skills as described in this unit. It may be required by some jurisdictions that RTOs provide a percentile graded result for the purpose of regulatory or licensing requirements.
Demonstrate an appropriate level of skills enabling employment
Conduct work observing the relevant Anti Discrimination legislation, regulations, polices and workplace procedures
Demonstrated consistent performance across a representative range of contexts from the prescribed items below:
Install CO2 refrigeration system components pipe work and associated equipment including :
A
Reading and interpreting drawings to pipe work layouts and apparatus locations.
B
Installing, connecting , securing and aligning components and equipment and ensuring that all equipment and pipe work is compliant with codes and regulations
C
Pressure testing entire system at the appropriate design test pressures using dry nitrogen
D
Removing system contaminants and evacuating
E
Selecting and using appropriate measuring devices correctly
F
Recording measurements
G
Using calculation methods accurately
H
Discharging / charging refrigerant / lubricants and pressure testing the system without damage to components
I
Locating and rectifying leaks
J
Using methodical and efficient commissioning techniques
K
Optimizing system performance and efficiency
L
Identifying the conditions of the refrigerant (R744) at various locations in the vapour compression and volatile secondary (liquid recirculation) system
M
Documenting operating conditions correctly (commissioning)
N
Dealing with unplanned events by drawing on essential knowledge and skills to provide appropriate solutions incorporated in the holistic assessment with the above listed items
Context of and specific resources for assessment
9.3)
This unit should be assessed as it relates to normal work practice using procedures, information and resources typical of a workplace. This should include:
OHS policy and work procedures and instructions.
Suitable work environment, facilities, equipment and materials to undertake actual work as prescribed by this unit.
These should be part of the formal learning/assessment environment.
Note:
Where simulation is considered a suitable strategy for assessment, conditions must be authentic and as far as possible reproduce and replicate the workplace and be consistent with the approved industry simulation policy.
Evidence should show demonstrated competency in installation techniques as well as Commissioning skills and a clear understanding of operating conditions of Carbon Dioxide vapour compression and volatile secondary (liquid recirculation/cascade) system/s.
Method of assessment
9.4)
This unit shall be assessed by methods given in Volume 1, Part 3 'Assessment Guidelines'.
Note:
Competent performance with inherent safe working practices is expected in the industry to which this unit applies. This requires assessment in a structured environment which is primarily intended for learning/assessment and incorporates all necessary equipment and facilities for learners to develop and demonstrate the essential knowledge and skills described in this unit.
Concurrent assessment and relationship with other units
9.5)
There are no concurrent assessment recommendations for this unit.
The critical aspects of occupational health and safety covered in unit UEENEEE001B and other discipline specific occupational health and safety units shall be incorporated in relation to this unit..
Replaced By
| State Code | National Code | Title | Type |
|---|---|---|---|
| OBX95 | UEERA0047 | Install and commission carbon dioxide refrigeration systems, components and associated equipment | Unit of competency |
| State Code | National Code | Title | Type |
|---|---|---|---|
| D635 | UEE32211 | Certificate III in Air-conditioning and Refrigeration | Qualification |
| D638 | UEE42911 | Certificate IV in Refrigeration and Air-conditioning Systems | Qualification |
| AC764 | UEESS00083 | Refrigeration-Air Conditioning - Install and Commission Carbon Dioxide Refrigeration Systems | Skill set |